Service Manual SiE 00-07. SiE 00-07 Table of Contents i Inverter K Series. After the repair work is complete, be sure to conduct a test operation to ensure that the equipment operates normally, and explain the cautions for operating the product to the customer 1.1.1 Caution in Repair.

Index:

  1. Split AC Error Codes
  2. L Series AC Error Codes
  3. Multi AC Error Codes
  4. VRV IV 4 Error Codes
  5. VRV III 3 Error Codes

1-Daikin Split AC Error Codes:

Error CodesProblem
00Normal
UAIndoor-outdoor Unit Combination Fault
U0Refrigerant Shortage
U2Drop Voltage Or Main Circuit Overvoltage
U4Failure Of Transmission (Between Indoor Unit And Outdoor Unit)
A1Indoor Pcb Defectiveness
A5High Pressure Control Or Freeze-up Protector
A6Fan Motor Fault
C4Faulty Heat Exchanger Temperature Sensor
C9Faulty Suction Air Temperature Sensor
EACooling-heating Switching Error
E1Circuit Board Fault
E5OL Started
E6Faulty Compressor Start Up
E7DC Fan Motor Fault
F3High Temperature Discharge Pipe Control
F6High Pressure Control (In Cooling)
H0Sensor Fault
H6Operation Halt Due To Faulty Position Detection Sensor
H8DC Current Sensor Fault
H9Faulty Suction Air Temperature Sensor
J3Faulty Discharge Pipe Temperature Sensor
J6Faulty Heat Exchanger Temperature Sensor
L3Electrical Parts Heat Fault
L4High Temperature At Inverter Circuit Heatsink
L5Output Overcurrent
P4Faulty Inverter Circuit Heatsink Temperature Sensor

Led On Outdoor Unit PCB


2- Daikin L Series AC Error Codes:

Error CodesMeaning
System Error Codes
00Normal
U0Refrigerant shortage
U2Low-voltage detection or over-voltage detection
U4Signal transmission error (between indoor unit and outdoor unit)
UAUnspecified voltage (between indoor unit and outdoor unit)
Indoor Unit Error Codes
A1Indoor unit PCB abnormality
A5Freeze-up protection control or heating peak-cut control
A6Fan motor or related abnormality
C4Indoor heat exchanger thermistor or related abnormality
C9Room temperature thermistor or related abnormality
Outdoor Unit Error Codes
E1Outdoor unit PCB abnormality
E5OL activation (compressor overload)
E6Compressor lock
E7DC fan lock
E8Input overcurrent detection
EAFourWay valve abnormality
F3Discharge pipe temperature control
F6High pressure control in cooling
H0Compressor system sensor abnormality
H6Position sensor abnormality
H8DC voltage / current sensor abnormality - CT or related abnormality
H9Outdoor temperature thermistor or related abnormality
J3Discharge pipe thermistor or related abnormality
J6Outdoor heat exchanger thermistor or related abnormality
L3Electrical box temperature rise
L4Radiation fin temperature rise
L5Output overcurrent detection
P4Radiation fin thermistor or related abnormality
U7Signal transmission error on outdoor unit PCB

Indoor Unit PCB Abnormality;

Remote Controller Display: A1

Supposed Causes:

  • Wrong models interconnected
  • Defective indoor unit PCB
  • Disconnection of connector
  • Reduction of power supply voltage

Remote Controller Display: A5

Supposed Causes:

  • Short-circuited air
  • Clogged air filter of the indoor unit
  • Dust accumulation on the indoor heat exchanger
  • Defective indoor heat exchanger thermistor
  • Defective indoor unit PCB

Remote Controller Display: A6

Supposed Causes:

  • Layer short inside the fan motor winding
  • Breaking of wire inside the fan motor
  • Breaking of the fan motor lead wires
  • Defective capacitor of the fan motor
  • Defective indoor unit PCB

Remote Controller Display: C4, C9

Supposed Causes:

  • Disconnection of connector
  • Defective thermistor
  • Defective indoor unit PCB

Remote Controller Display: U0

Supposed Causes:

  • Disconnection of the discharge pipe thermistor, indoor or outdoor heat exchanger thermistor, room or outdoor temperature thermistor
  • Closed stop valve
  • Refrigerant shortage (refrigerant leakage)
  • Poor compression performance of compressor
  • Defective electronic expansion valve

Remote Controller Display: U2

Supposed Causes:

  • Supply voltage is not as specified.
  • Defective DC voltage detection circuit
  • Defective over-voltage detection circuit
  • Defective PAM control part
  • Disconnection of compressor harness
  • Noise
  • Momentary fall of voltage
  • Momentary power failure
  • Defective indoor unit PCB

Remote Controller Display: U4

Supposed Causes:

  • Wiring error
  • Breaking of the connection wires between the indoor and outdoor units (wire No. 3)
  • Defective outdoor unit PCB
  • Defective indoor unit PCB
  • Disturbed power supply waveform

Remote Controller Display: U7

Supposed Causes: Defective outdoor unit PCB

Remote Controller Display: UA

Supposed Causes:

  • Wrong models interconnected
  • Wrong wiring of connecting wires
  • Wrong indoor unit PCB or outdoor unit PCB mounted
  • Defective indoor unit PCB
  • Defective outdoor unit PCB

Remote Controller Display: E1

Supposed Causes:

  • Defective outdoor unit PCB
  • Broken harness between PCBs
  • Noise
  • Momentary fall of voltage
  • Momentary power failure, etc

Remote Controller Display: E5

Supposed Causes:

  • Defective discharge pipe thermistor
  • Defective electronic expansion valve or coil
  • Defective FourWay valve or coil
  • Defective outdoor unit PCB
  • Refrigerant shortage
  • Water mixed in refrigerant
  • Defective stop valve

Remote Controller Display: E6

Supposed Causes:


  • Compressor locked
  • Compressor harness disconnected

Remote Controller Display: E7

Supposed Causes:

  • Foreign matter stuck in the fan
  • Defective fan motor
  • Defective outdoor unit PCB

Remote Controller Display: E8

Supposed Causes:

Car Service Manual

  • Outdoor temperature is out of operation range.
  • Defective compressor
  • Defective power module
  • Defective outdoor unit PCB
  • Short circuit

Remote Controller Display: EA

Supposed Causes:

  • Disconnection of fourway valve coil
  • Defective fourway valve, coil, or harness
  • Defective outdoor unit PCB
  • Defective thermistor
  • Refrigerant shortage
  • Water mixed in refrigerant
  • Defective stop valve

Remote Controller Display: F3

Supposed Causes:

  • Defective discharge pipe thermistor
  • Defective electronic expansion valve or coil
  • Refrigerant shortage
  • Defective fourway valve
  • Water mixed in refrigerant
  • Defective stop valve
  • Defective outdoor unit PCB

Remote Controller Display: F6

Supposed Causes:

Vrv
  • The installation space is not large enough.
  • Dirty outdoor heat exchanger
  • Defective outdoor fan motor
  • Defective stop valve
  • Defective electronic expansion valve or coil
  • Defective outdoor heat exchanger thermistor
  • Defective outdoor unit PCB

Remote Controller Display: H0

Supposed Causes:

  • Broken or disconnected harness
  • Defective outdoor unit PCB

Remote Controller Display: H6

Supposed Causes:

  • Disconnection of the compressor relay cable
  • Defective compressor
  • Defective outdoor unit PCB
  • Start-up failure caused by the closed stop valve
  • Input voltage is outside the specified range.

Remote Controller Display: H8

Supposed Causes: Defective outdoor unit PCB

Remote Controller Display: H9, J3, J6, P4

Supposed Causes:

  • Disconnection of the connector for the thermistor
  • Defective thermistor corresponding to the error code
  • Defective heat exchanger thermistor in the case of J3 error
  • Defective outdoor unit PCB

Remote Controller Display: L3

Supposed Causes:

  • Defective outdoor fan motor
  • Short circuit
  • Defective radiation fin thermistor
  • Disconnection of connector
  • Defective outdoor unit PCB

Remote Controller Display: L4

Supposed Causes:

  • Defective outdoor fan motor
  • Short circuit
  • Defective radiation fin thermistor
  • Disconnection of connector
  • Defective outdoor unit PCB
  • Silicon grease is not applied properly on the radiation fin after replacing the outdoor unit PCB.

Remote Controller Display: L5

Supposed Causes:

  • Poor installation condition
  • Closed stop valve
  • Defective power module
  • Wrong internal wiring
  • Abnormal power supply voltage
  • Defective outdoor unit PCB
  • Defective compressor

Service Check Function

  1. When the timer cancel button is held down for 5 seconds, 00 is displayed on the temperature display screen.
  2. Press the timer cancel button repeatedly until a long beep sounds.

3-Daikin Multi-Split Type AC Error Codes:

Daikin’s multi-split type air conditioning systems offer superior performance, energy-efficiency, and comfort in stylish solutions conforming to all interior spaces and lifestyles. An extensive product lineup utilizes Daikin technology for lower costs and environmental impact. Advanced inverter and heat pump technologies achieve greater efficiency and energy-savings at lower costs. A broad array of models allows the perfect match of style and performance to any interior space.

2/3/4MXS-G/J Series/Heat Pump

Error CodesProblem
00Normal
UAIndoor-Outdoor Unit Combination Fault
U0Refrigerant Shortage
U2Drop Voltage or Main Circuit Overvoltage
U4Failure Of Transmission (Between Indoor Unit and Outdoor Unit)
A1Indoor PCB Defectiveness
A5High Pressure Control or Freeze-up Protector
A6Fan Motor Fault
C4Faulty Heat Exchanger Temperature Sensor
C9Faulty Suction Air Temperature Sensor
EACooling-Heating Switching Error
E1Circuit Board Fault
E5OL Started
E6Faulty Compressor Start Up
E7DC Fan Motor Fault
E8Overcurrent Input
F3High Temperature Discharge Pipe Control
F6High Pressure Control (In Cooling)
H0Sensor Fault
H6Operation Halt Due To Faulty Position Detection Sensor
H8DC Current Sensor Fault
H9Faulty Suction Air Temperature Sensor
J3Faulty Discharge Pipe Temperature Sensor
J6Faulty Heat Exchanger Temperature Sensor
L3Electrical Parts Heat Fault
L4High Temperature At Inverter Circuit Heatsink
L5Output Overcurrent
P4Faulty Inverter Circuit Heatsink Temperature Sensor

4-Daikin VRV IV (4) Error Codes:


The following will be displayed on the screen when an error (or a warning) occurs during operation. Check the error code and take the corrective action specified for the particular model. If unit stops due to an error, the operation indicating LED on the signal receiving part of indoor unit blinks. The error code can be determined by following the procedure described below. (The error code is displayed when an operation error has occurred. In normal condition, the error code of the last problem is displayed.)

Error CodesProblem
A1EEPROM failure (indoor)
A3Drain system malfunction (indoor)
A6Fan motor malfunction (indoor)
A7Swing flap motor malfunction (indoor)
A9Expansion valve malfunction (indoor)
AFDrain malfunction (indoor unit)
AHFilter dust chamber malfunction (indoor)
AJCapacity setting malfunction (indoor)
C1Transmission malfunction between main PCB and sub PCB (indoor)
C4Heat exchanger thermistor malfunction (indoor; liquid)
C5Heat exchanger thermistor malfunction (indoor; gas)
C9Suction air thermistor malfunction (indoor)
CADischarge air thermistor malfunction (indoor)
CEMovement detector or floor temperature sensor malfunction (indoor)
CJUser interface thermistor malfunction (indoor)
E1PCB malfunction (outdoor)
E2Current leakage detector was activated (outdoor)
E3High pressure switch was activated
E4Low pressure malfunction (outdoor)
E5Compressor lock detection (outdoor)
E7Fan motor malfunction (outdoor)
E9Electronic expansion valve malfunction (outdoor)
F3Discharge temperature malfunction (outdoor)
F4Abnormal suction temperature (outdoor)
F6Refrigerant overcharge detection
H3High pressure switch malfunction
H4Low pressure switch malfunction
H7 Fan motor trouble (outdoor)
H9 Ambient temperature sensor malfunction (outdoor)
J1Pressure sensor malfunction
J2Current sensor malfunction
J3Discharge temperature sensor malfunction (outdoor)
J4Heat exchanger gas temperature sensor malfunction (outdoor)
J5Suction temperature sensor malfunction (outdoor)
J6De-icing temperature sensor malfunction (outdoor)
J7Liquid temperature sensor (after subcool HE) malfunction (outdoor)
J8 Liquid temperature sensor (coil) malfunction (outdoor)
J9 Gas temperature sensor (after subcool HE) malfunction (outdoor)
JA High pressure sensor malfunction (S1NPH)
JCLow pressure sensor malfunction (S1NPL)
L1 INV PCB abnormal
L4Fin temperature abnormal
L5 Inverter PCB faulty
L8Compressor over current detected
L9 Compressor lock (startup)
LC Transmission outdoor unit - inverter: INV transmission trouble
P1 INV unbalanced power supply voltage
P2Autocharge operation related
P4Fin thermistor malfunction
P8Autocharge operation related
P9 Autocharge operation related
PEAutocharge operation related
PJ Capacity setting malfunction (outdoor)
U0 Abnormal low pressure drop, faulty expansion valve
U1Reversed power supply phase malfunction
U2INV voltage power shortage
U3System test run not yet executed
U4 Faulty wiring indoor/outdoor
U5Abnormal user interface - indoor communication
U7Faulty wiring to Q1/Q2
U8Abnormal main-sub user interface communication
U9System mismatch. Wrong type of indoor units combined. Indoor unit malfunction
UA Connection malfunction over indoor units or type mismatch
UCCentralized address duplication
UEMalfunction in communication centralized control device - indoor unit
UFAuto address malfunction (inconsistency)
UH Auto address malfunction (inconsistency)

5-Daikin VRV III (3) Error Codes:

If operation stops due to malfunction, the remote controlís operation LED blinks, and malfunction code is displayed. (Even if stop operation is carried out, malfunction contents are displayed when the inspection mode is entered.)

1. Pressing the INSPECTION/TEST button will blink the check indication.

2. While in check mode, pressing and holding the ON/OFF button for a period of five seconds or more will clear the failure history indication shown above.

Error CodesProblem
A0Error of external protection device
A1PC board defect, E2 PROM defect
A3Malfunction of drain level control system (S1L)
A6Fan motor (M1F) lock, overload
A7Malfunction of swing flap motor (M1S)
A9Malfunction of moving part of electronic expansion valve (Y1E)
AFDrain level above limit
AJ Malfunction of capacity setting
C4Malfunction of thermistor (R2T) for heat exchange
C5Malfunction of thermistor (R3T) for gas pipes
C9 Malfunction of thermistor (R1T) for air inlet
CAMalfunction of thermistor for air inlet
CJ898 Malfunction of thermostat sensor in remote control
E1PC board defect
E3 Actuation of high pressure switch
E4Actuation of low pressure sensor
E5Compressor motor lock
E6Standard compressor lock or over current
E7Malfunction of outdoor unit fan motor
E9Malfunction of moving part of electronic expansion valve (Y1E, Y2E)
F3Abnormal discharge pipe temperature
F6Refrigerant overcharged
H3Failure of high pressure switch
H4Actuation of low pressure switch
H7 Abnormal outdoor fan motor signal
H9Malfunction of thermistor (R1T) for outdoor air
J2Current sensor malfunction
J3 Malfunction of discharge pipe thermistor
J5 Malfunction of thermistor (R3T, R5T) for suction pipe
J6Malfunction of thermistor (R6T) for heat exchanger
J7Malfunction of receiver outlet liquid pipe thermistor (R7T)
J9Malfunction of subcooling heat exchanger gas pipe thermistor
JAMalfunction of discharge pipe pressure sensor
JCMalfunction of suction pipe pressure sensor
L0Inverter system error
L1 Malfunction of PC board
L4 Malfunction of inverter radiating fin temperature rise
L5 DC output overcurrent of inverter compressor
L8Inverter current abnormal
L9Inverter start up error
LAMalfunction of power unit
LCMalfunction of transmission between inverter and control PC board
P1 High voltage of capacitor in main inverter circuit
U0Low pressure drop due to refrigerant shortage or electronic expansion valve failure
U1Reverse phase / open phase
U2Power supply insufficient or instantaneous failure
U3Check operation is not completed
U4Malfunction of transmission between indoor and outdoor units
U5Malfunction of transmission between remote control and indoor unit
U6 Failure of remote control PC board or setting during control by remote control
U7 Malfunction of transmission between outdoor units
U8Malfunction of transmission between main and sub remote controls
U9 Malfunction of transmission between indoor unit and outdoor unit in the same system
UA Improper combination of indoor and outdoor units,indoor units and remote control
UCAddress duplication of central remote control
UE Malfunction of transmission between central remote control and indoor unit
UFRefrigerant system not set, incompatible wiring /piping
UHMalfunction of system, refrigerant system address undefined
UE Malfunction of transmission between central remote control and indoor unit
M1Central remote control PC board defect Schedule timer PC board defect
M8Malfunction of transmission between optional controllers for centralized control
MAImproper combination of optional controllers for centralized control
MCAddress duplication, improper setting
64 Indoor unitís air thermistor error
65 Outside air thermistor error
68Malfunction of HVU
6ADamper system alarm
6A Damper system + thermistor error
6FMalfunction of simple remote control
94Internal transmission error

Daikin AC Troubleshooting


The following incidents do not indicate a malfunctioning air conditioner and have explanations. The air conditioner can continue to operate.

Case: Operation does not start soon.

Explanation: This is to protect the air conditioner. You should wait for about 3 minutes.

Case: Hot air does not fl ow out soon after the start of HEAT operation.

Explanation: The air conditioner is warming up. You should wait for 1 to 4 minutes.

Case: The HEAT operation stops suddenly and a flowing sound is heard.

Explanation: The system is taking away the frost on the outdoor unit. You should wait for about 4 to 12 minutes.

Case: The outdoor unit emits water or steam.

Explanation:

  • In HEAT operation; The frost on the outdoor unit melts into water or steam when the air conditioner is in defrost operation.
  • In COOL or DRY operation; Moisture in the air condenses into water on the cool surface of outdoor unit piping and drips.

Case: Mist comes out of the indoor unit.

Explanation:

  • This happens when the air in the room is cooled into mist by the cold airflow during COOL operation.
  • This is because the air in the room is cooled by the heat exchanger and becomes mist during defrost operation.

Case: The indoor unit gives out odor

Explanation:

  • This happens when smells of the room, furniture, or cigarettes are absorbed into the unit and discharged with the airflow. If this happens, it is recommended to have the indoor unit washed by a technician. Consult the service shop where you purchased the air conditioner.

Case: The outdoor fan rotates while the air conditioner is not in operation.

Explanation:

  • After operation is stopped; The outdoor fan continues rotating for another 60 seconds for system protection.
  • While the air conditioner is not in operation; When the outdoor temperature is very high, the outdoor fan starts rotating for system protection.

Case: Operation stopped suddenly. (OPERATION lamp is on.)

Explanation: For system protection, the air conditioner may stop operating on a sudden large voltage fluctuation. It automatically resumes operation in about 3 minutes.

Case: No remote controller signals are displayed. Remote controller sensitivity is low. Display is low in contrast or blacked out. Display runs out of control.

Explanation: The batteries are dying and the remote controller is malfunctioning. Replace all the batteries with new size batteries, AAA.LR03 (alkaline). For details, refer to set the batteries of this manual.

Case: Possible sounds.

Explanation:

  • Flowing water; Generated because the refrigerant in the air conditioner is flowing. This is a pumping sound of the water in the air conditioner and heard when the water is pumped out from the air conditioner in cooling or drying operation. The refrigerant flows in the air conditioner even if the air conditioner is not working when the indoor units in other rooms are in operation.
  • Blowing; Generated when the flow of the refrigerant in the air conditioner is switched over
  • Pinging; Generated when the size of the air conditioner slightly expands or shrinks as a result of temperature changes.

Case: The air conditioner does not operate

Check:

  • Is a breaker off or a fuse blown?
  • Is there a power failure?
  • Are batteries set in the remote controller?
  • Is the timer setting correct?

Case: Cooling (Heating) effect is poor

Check:

  • Are the air fi lters clean?
  • Is there anything to block the air inlet or the outlet of the indoor and the outdoor units?
  • Is the temperature setting appropriate?
  • Are the windows and doors closed?
  • Are the airfl ow rate and the airfl ow direction set appropriately?

Case: Operation stopped suddenly

Daikin Vrv Iv Service Manual

Check:

  • Are the air fi lters clean?
  • Is there anything to block the air inlet or the outlet of the indoor and the outdoor units?
  • Clean the air fi lters or take all obstacles away and turn the breaker off. Then turn it on again and try operating the air conditioner with the remote controller. If the lamp still flashes, call the service shop where you purchased the air conditioner.
  • Are operation modes all the same for indoor units connected to outdoor units in the multi system?

Case: An abnormal functioning happens during operation

Check: The air conditioner may malfunction with lightning or radio waves. Turn the breaker off, turn it on again and try operating the air conditioner with the remote controller.

Case: The louvers do not immediately swing. The louvers move soon after startup

Check: The air conditioner is adjusting the louvers position. The louvers will start moving soon